Omron Q2A Series Technical Manual page 455

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

No.
Name
(Hex.)
L8-09
Ground Fault Selection
(04B5)
L8-10
Fan Operate Selection
(04B6)
L8-11
Fan Off-Delay Time
(04B7)
L8-12
Ambient Temperature
Setting
(04B8)
L8-15
oL2@LoSpeed Selection
(04BB)
L8-18
Soft CurrLim Selection
(04BE)
L8-19
Frq Reduct@oHPre-
Alarm
(04BF)
L8-20
CF / STPo Selection
(04C0)
Expert
L8-27
OverCurr Det Gain
(04DD)
L8-29
LF2 Unbalance Selection
(04DF)
L8-31
LF2 Detect Time
(04E1)
L8-32
Fan Failure Selection
(04E2)
L8-35
Installation Selection
(04EC)
L8-38
Carrier Reduction Mode
(04EF)
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to enable and disable ground fault protection.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets operation of the heatsink cooling fan.
1 : Dur Run (OffDly)
2 : Always On
3 : Fan ON @Heating of Drive
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time that the drive will wait before stopping the cooling fan after
cancelling the Run command when L8-10 = 1 [Fan Operate Selection = Dur Run
(OffDly)].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the ambient temperature of the drive installation area.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to decrease drive overload at low speeds to prevent damage to the
main circuit transistor during low speed operation (at 6 Hz or slower) to prevent oL2
[Drive Overloaded].
Note:
Contact the manufacturer before disabling this function at low speeds. If you
frequently operate drives with high output current in low speed ranges, it can cause
heat stress and decrease the life span of drive IGBTs.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Set the software current limit selection function to prevent damage to the main circuit
transistor caused by too much current.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the ratio at which the drive derates the frequency reference when during an oH
alarm.
V/f
CL-V/f
OLV
CLV
AOLV
Sets operation after the drive detects a CF fault when A1-02 = 4 [Control Method =
Adv OLVector].
1 : Disabled
2 : CF/STPo Detection Enabled
3 : CF ALM/Stop
V/f
CL-V/f
OLV
CLV
AOLV
Sets the PM motor overcurrent detection level as a percentage of the motor rated current
value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to detect LF2.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the LF2 [Output Current Imbalance] detection time.
V/f
CL-V/f
OLV
CLV
AOLV
Sets operation when the drive detects FAn [Internal Agitating Fan Fault].
0 : Ramp->Stop
1 : Coast->Stop
2 : Fast Stop (C1-09)
3 : Alarm Only
4 : Run@L8-19 Rate
V/f
CL-V/f
OLV
CLV
AOLV
Sets the type of drive installation.
0 : IP00/IP20/Open-Chassis
1 : Side-by-Side Mounting
2 : IP21/NEMA Type 1/IP55
3 : Finless/Ext.Heatsink
V/f
CL-V/f
OLV
CLV
AOLV
Sets the carrier frequency reduction function. The drive reduces the carrier frequency
when the output current is more than a specified level.
0 : Disabled
1 : Enable<6 Hz
2 : Enab@AllSpeed
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.9 L: PROTECTION
Default
Ref.
(Range)
Determined by o2-04
776
(0, 1)
1
776
(1 - 3)
60 s
776
(0 - 300 s)
40 °C
776
(-10 - +50 °C)
1
776
(0, 1)
0
777
(0, 1)
0.8
777
(0.1 to 0.9)
Determined by A1-02
777
(1 - 3)
300.0%
777
(0.0 - 400.0%)
1
778
(0, 1)
3
778
(1 to 100)
1
778
(0 - 4)
Determined by the drive
779
model
(0 - 3)
Determined by A1-02,
779
C6-01, and o2-04
(0 - 2)
455