7026 Model H70 (Enterprise Server) - IBM RS/60000 Series Site And Hardware Planning Information

Table of Contents

Advertisement

7026 Model H70 (Enterprise Server)

Dimensions
Height
Width
Depth
Weight
Minimum configuration
Maximum configuration
Electrical
Power source loading typical ¹ in kVA
Power source loading maximum ¹ in
kVA
Voltage range (V ac)
Frequency (hertz)
Thermal output (typical)
Thermal output (maximum)
Power requirements (typical)
Power requirements (maximum)
Power factor
Inrush current²
Maximum altitude³
Temperature Requirements³
Humidity Requirements
(Noncondensing)
Wet Bulb
Noise Emissions⁴
L
WAd
L
pAm
<L
>
pA
m
Impulsive or prominent discrete tones
Clearances
Install/Air Flow
Service
1. The power source loading is calculated using the power factor = 0.94.
2. Inrush currents occur only at initial application of power, no inrush occurs during normal power off-on cycle.
3. For altitudes above 915 meters, the maximum temperature limit is derated by 1 degree C for every 137 meters of
elevation above 915 meters.
4. See "Noise Emission Notes" on page 336 for definitions of noise emissions positions.
76
Site and Hardware Planning Information
Operating
10 to 40°C
(50 to 104°F)
Operating
8 to 80%
27°C (80.6°F)
Operating
6.2 bels
N/A
43 dBA
No
Front
Back
Maintenance of proper service clearances should allow proper air flow.
(See service clearances for the "7015 System Rack R00" on page 41)
350 mm 13.8 in.
8 (EIA Units)
443 mm 17.4 in.
875 mm 34.2 in.
71 kg 157 lbs.
89 kg 195 lbs.
0.46
0.691
200 to 240
50 or 60
1485 Btu/hr
2818 Btu/hr
434 watts
650 watts
0.9 - 0.98
50 amps
915 m (3000 ft.)
Non-Operating
10 to 52°C
(50 to 125.6°F)
Non-Operating
8 to 80%
27°C (80.6°F)
Idle
5.9 bels
N/A
40 dBA
Left
No
Right

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

7006 42tEserver pseries7006 42w7007 powerportable n407008 powerstation m207008 powerstation m2a ... Show all

Table of Contents