IBM RS/60000 Series Site And Hardware Planning Information page 220

Table of Contents

Advertisement

The following table lists maximum operating temperatures for system features at various altitudes.
0
FC 6120
28°C
(82°F)
FC 6134
26°C
(79°F)
202
Site and Hardware Planning Information
305 m
610 m
(1000 ft)
(2000 ft)
27°C
27°C
(81°F)
(81°F)
25°C
25°C
(77°F)
(77°F)
914 m
1219 m
(3000 ft)
(4000 ft)
26°C
26°C
(79°F)
(79°F)
24°C
24°C
(75°F)
(75°F)
1524 m
1829 m
(5000 ft)
(6000 ft)
25°C
24°C
(77°F)
(75°F)
23°C
22°C
(73°F)
(72°F)
2134 m
(7000 ft)
24°C
(75°F)
22°C
(72°F)