IBM RS/60000 Series Site And Hardware Planning Information page 213

Table of Contents

Advertisement

The minimum service clearance for single-frame and double-frame systems with acoustical doors is shown
in the following illustration.
f
e
6.6 in
(168 mm)
A
26 in.
(660 mm)
d
f
Single-Frame System
with Acoustical Doors
Refer to the illustration in "Guide for Raised-Floor Preparation" on page 182 for service clearances shown
in a raised-floor installation.
e
6.6 in
(168 mm)
A
2.6 in
(66 mm)
d
Single-Frame System
with Acoustical Doors
(alternative right-side
service clearance)
d=1143 mm (45.0 in.)
e=914 mm (36.0 in.)
f=1511 mm (59.5 in.)
f (alternate)=1765 mm (69.5 in.)
G=1808 mm (71.2 in.)
f (alternate)
6.6 in
(168 mm)
26 in.
(660 mm)
f (alternate)
Chapter 2. Physical Characteristics of Systems
g
e
A
B
d
g
Double-Frame System
with Acoustical Doors
2.6 in
(66 mm)