5.7 Auto-Tuning Fault Detection

5.7

Auto-Tuning Fault Detection

◆ Auto-Tuning Codes, Causes, and Possible Solutions

The Auto-Tuning faults are shown below. When the following faults are detected, the fault is displayed on the digital
operator and the motor coasts to a stop. Auto-Tuning faults do not trigger a contact terminal set for fault or alarm output.
An End error (where
discrepancy in the calculations the drive made. If there is found to be no problem on checking the cause, use the tuning
value as it stands. If there is judged to be a problem, implement countermeasures and then perform Auto-Tuning again, or
set (input) the motor parameters manually.
Digital Operator Display
End1
Cause
The torque reference exceeded 20% during
Auto-Tuning.
The results from Auto-Tuning the no-load
current exceeded 80%.
Digital Operator Display
End2
Cause
Motor data or data entered during Auto-Tuning
was incorrect.
Results from Auto-Tuning are outside the
parameter setting range, assigning the iron-core
saturation coefficients (E2-07 and E2-08) a
temporary value.
Digital Operator Display
End3
Cause
The correct current rating printed on the
nameplate was not entered into T1-04.
Digital Operator Display
End4
Cause
In Stationary Auto-Tuning, the slip value
resulted in 0.2 Hz or less.
The slip that was calculated is outside the
allowable range.
The value after the compensation in E2-08
(Motor Iron-Core Saturation Coefficient 2)
exceeds the upper and lower limits.
The measured value of secondary resistance is
negative.
Digital Operator Display
End5
Cause
The calculated resistance value is outside the
allowable range.
174
is a numeric character) indicates that although Auto-Tuning has been completed, there is some
Table 5.16 Auto-Tuning Codes, Causes, and Possible Solutions
Excessive V/f Setting (detected only during Rotational Auto-Tuning, and displayed after
Auto-Tuning is complete)
• Before Auto-Tuning the drive, verify the information written on the motor nameplate and enter
that data to T1-03 through T1-05.
• Enter proper information to parameters T1-03 to T1-05 and repeat Auto-Tuning.
• If possible, disconnect the motor from the load and perform Auto-Tuning. If the load cannot be
uncoupled, use the current Auto-Tuning results.
Motor Iron Core Saturation Coefficient Error (detected only during Rotational Auto-Tuning and
displayed after Auto-Tuning is complete)
• Make sure the data entered to the T1 parameters match the information written on the motor
nameplate.
• Enter the correct information and restart Auto-Tuning.
• Check and correct faulty motor wiring.
• Disconnect the motor from machine and perform Rotational Auto-Tuning.
Rated Current Setting Alarm (displayed after Auto-Tuning is complete)
• Check the setting of parameter T1-04.
• Check the motor data and repeat Auto-Tuning.
Adjusted Slip Calculation Error
• Check the value input for T1-
• Execute Rotational Auto-Tuning.
Resistance Tuning Error
Double-check the data entered for the Auto-Tuning process.
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions
.
Error Name
Possible Solutions
YASKAWA ELECTRIC TOEP C710687 02B FSDrive-MV1000 Instructions

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cimr-mv2 series

Table of Contents