Checking the safety valve function
Checking the electrical connections for firm seating
Checking all gas equipment for tightness at operating pressure
Danger
Escaping gas leads to a risk of explosion.
Check gas equipment (including inside the appli-
ance) for leaks.

Fitting the front panel

See page 30.

Checking the combustion quality

The electronic combustion controller automatically
ensures optimum combustion quality. During commis-
sioning/maintenance, only the combustion values need
to be checked. To do this, test the CO content and CO
or O
content, and record these in the report on
2
page 117.
Permissible CO content
The CO content must be < 1000 ppm for all gas types.
Permissible CO
or O
2
2
Operation with natural gas
Rated heating out-
CO
put (kW)
Upper heating out-
put
11
7.3 - 10.5
19
7.5 - 10.5
25
7.5 - 10.5
32
7.3 - 10.0
Operation with LPG
CO
content: 8.4 - 11.8 %
2
O
content: 3.1 - 8.1 %
2
content
content (%)
2
Lower heating out-
put
7.5 - 10.5
7.5 - 10.5
7.5 - 10.5
7.5 - 10.5
Commissioning, inspection, maintenance
Note
Only use suitable and approved leak detection agents
(EN 14291) and devices for the tightness test. Leak
detection agents with unsuitable constituents (e.g.
nitrides, sulphides) can cause material damage.
Remove residues of the leak detection agent after test-
ing.
Note
To prevent operating faults and damage, operate the
appliance with uncontaminated combustion air.
2
O
content (%)
2
Upper heating out-
put
2.1 - 7.9
2.1 - 7.6
2.1 - 7.6
3.1 - 7.9
If the actual CO, CO
2
respective ranges, proceed as follows:
Check the balanced flue system for tightness; see
page 47.
Check the ionisation electrode and connecting cable;
see page 50.
Lower heating out-
put
2.1 - 7.6
2.1 - 7.6
2.1 - 7.6
2.1 - 7.6