Solar
(cont.)
1127.0 "Frost protection function for solar circuit"
Setting
Off
On
1136.2 "Heat transfer medium, solar circuit"
Setting
1394.0 "DHW set temperature for reheating suppression"
Setting
40 °C
1492.0 "Start temperature differential, solar circuit pump"
Setting
8 K
1492.1 "Stop temperature differential, solar circuit pump"
Setting
4 K
1505.0 "Stagnation time reduction"
Setting
5 K
Explanations
Frost protection function for the solar circuit:
0
Not active
1
Enabled
Not required for Viessmann heat transfer medium
Explanations
Setting is required for calculating the solar yield
0
Calculation of solar yield with water as heat transfer
medium
1
Calculation of solar yield with Viessmann heat transfer
medium
Explanations
40
DHW set temperature for reheating suppression.
Above the selected set temperature reheating sup-
pression is active.
0 to 95
DHW set temperature adjustable from 0 to 95 °C
Explanations
Start temperature differential between the actual tem-
perature of temperature sensor
temperature of collector temperature sensor
8
Factory setting: 8 K
2 to 30
Start temperature differential adjustable from 2 to 30 K
Explanations
Stop temperature differential between the actual tem-
perature of temperature sensor
temperature of collector temperature sensor
4
Factory setting 4 K
1 to 29
Stop temperature differential adjustable from 1 to 29 K
Explanations
Temperature differential between the actual tempera-
ture of the collector temperature sensor and the set
maximum collector temperature.
Reduction in the speed of the solar circuit pump to
protect system components and heat transfer medium
5
Factory setting: 5 K
0
Stagnation time reduction not active
1 to 40
Temperature differential adjustable from 1 to 40 K
System configuration (parameters)
%
and the actual
and the actual
%
&
&
71