Condensate Connection; Filling The Trap With Water; Flue Gas Connection - Viessmann Vitodens 200-W B2HE Installation And Service Instructions Manual

Wall mounted gas condensing boiler
Hide thumbs Also See for Vitodens 200-W B2HE:
Table of Contents

Advertisement

Condensate connection

Fig. 10

Filling the trap with water

Fig. 11
Note
If there is a risk of frost, only fill the trap just before
commissioning.

Flue gas connection

Note
The "System certification" and "Skoberne GmbH flue
system" labels enclosed with the technical documenta-
tion may only be used in conjunction with the
Viessmann flue system made by Skoberne.
1. Push the supplied drain hose on to the drain con-
nector.
2. Connect the drain hose with a constant fall and a
pipe vent to the public sewage system or to a neu-
tralising system.
Note
Route the onward drain line inside the building as
far as possible.
If the onward drain line is routed outside the build-
ing:
Use a min. Ø 30 mm line.
Protect the line from frost.
Keep the line as short as possible.
!
Please note
The drain hose is used to route away any
hot water discharged from the safety valve.
Lay and secure the drain hose in a way that
prevents any risk of scalding.
Note
Observe local waste water regulations.
Pour at least 0.3 l of water into the flue gas connection.
!
Please note
During commissioning, flue gas may escape
from the condensate drain.
Always fill the trap with water before commis-
sioning.
Connecting the balanced flue pipe
Flue system installation instructions
Installation sequence
17