Installation sequence
Electrical connections

On-site connections on HMU heat management unit

Fig. 15
Diaphragm grommets, 230 V cables
A
Diaphragm grommets, extra low voltage (ELV)
B
Open diaphragm grommets as required. Thread
through only one cable at a time without a plug.
Ensure diaphragm grommets are airtight. If required,
remove plug from cable. After threading the cable
through, re-fit the plug to the wire ferrules.
Required plugs are supplied in separate packaging.
For cables without strain relief bushings, provide
strain relief in the wiring chamber in the form of cable
ties.

Outside temperature sensor

Fitting location for outside temperature sensor
North or north-westerly wall, 2 to 2.5 m above
ground level; in multi storey buildings, in the upper
half of the second floor
Not above windows, doors or vents
22
(cont.)
A
B
!
C
D
Plug-in connection on underside of appliance
C
Plug for connecting sensors and PlusBus
D
Remove plug from the pack of installation compo-
nents.
Not immediately below balconies or gutters
Never render over
Outside temperature sensor connection
2-core lead, length up to 35 m with a cross-section
2
of 1.5 mm