3.4
Current Protection: Sensitive Earth Fault (67SEF, 51SEF,
50SEF)
Current for the Sensitive Earth Fault (SEF) elements is measured directly via a dedicated current analogue input
which requires different hardware that must be specially ordered. SEF elements measure the fundamental
frequency RMS current.
3.4.1

Directional Control of Sensitive Earth Fault Protection (67SEF)

The directional element produces forward and reverse outputs for use with SEF elements. These outputs can be
mapped as controls to each shaped and instantaneous element.
If a protection element is set as non-directional then it will operate independently of the output of the directional
detector. However, if a protection element is programmed for forward directional mode then operation will occur
only for a fault lying within the forward operate zone. Conversely, if a protection element is programmed for
reverse directional mode then operation will occur only for a fault lying within the reverse operate zone. Typically
the forward direction is defined as being 'away' from the busbar or towards the protected zone.
The forward directional zone of the relay is defined by the characteristic angle setting which is the angle by which
the polarising voltage differs from the operating current. The forward directional zone is symmetrical around the
characteristic angle with angular limits defined in the performance specification. The reverse operate zone is the
mirror image of the forward zone.
The directional sensitive earth fault elements use zero phase sequence (ZPS) polarising.
Voltage polarisation is achieved for the earth-fault elements by comparison of the appropriate current with its
equivalent voltage:
I
~ V
0
0
The characteristic angle can be user programmed to any angle between -95° and +95° using the 67SEF Char
Angle setting. The voltage is the reference phasor (V
adjust the forward and reverse zones.
The centre of the forward zone is set by (V
I
Angle for maximum sensitivity i.e.
fault
For fault current of -15° (I lagging V by 15°) a 67SEF Char Angle of -15° is required for maximum
sensitivity.
OR
For fault current of -45° (I lagging V by 45°) a 67SEF Char Angle of -45° is required for maximum
sensitivity.
Minimum Polarising Voltage
The 67SEF Minimum Voltage setting defines the minimum polarising voltage level. Where the measured
polarising voltage is below this level no directional output is given and. Operation of protection elements set as
directional will be inhibited. This prevents mal-operation under fuse failure/MCB tripped conditions where noise
voltages can be present.
V
L1
V
L2
V
L3
IL
(I
)
4
SEF

Figure 3-11 Logic Diagram: SEF Directional Element (67SEF)

©2018 Siemens Protection Devices Limited
Angle + 67SEF Char Angle) and should be set to correspond with
ref
V
Sequence
0
Filters
) and the 67SEF Char Angle setting is added to this to
ref
67SEF
67SEF Charact. Angle
67SEF Min. Voltage
fwd
rev
7SR10 Description of Operation
67SEF Fwd
67SEF Rev
Chapter 1 Page 37 of 77