3.5
74TCS & 74CCS Trip & Close Circuit Supervision
3.5.1

Reference

Parameter
t
Delay setting
d
3.5.2

Operate and Reset Time

Attribute
t
Element basic operate time
basic
t
Operate time following delay
op
Repeatability
Variation
3.6

81HBL2 Inrush Detector

3.6.1
Reference
Parameter
Setting
nd
I
(Ratio of 2
Harmonic current to
Fundamental component current)
3.6.2
Operate and Reset Time
Attribute
t
Element basic operate time
basic
Reset Time
NOTE:
Fundamental current should be minimum 0.1xIn for better inrush accuracy.
© 2018 Siemens Protection Devices Limited
-10 °C to +60 °C
f
± 5 %
nom
Value
0, 0.02...60 s
Value
30 ms ± 10 ms
t
+ t
, ± 1 % or ± 10 ms
basic
d
± 1 % or ± 10 ms
≤ 5 %
≤ 5 %
Value
0.10, 0.11... 0.5
Value
Will pick-up before operation of any protection element due
to magnetic inrush
Will operate until drop-off of any protection element due to
magnetic inrush
7SR10 Performance Specification