Scheme 3 (Comprehensive)
+
R
R
Scheme 3 provides full Trip supervision with the circuit breaker Open or Closed.
5.4.2

Close Circuit Supervision Connections

+
R
Close circuit supervision with the circuit breaker Open or Closed.
NOTE:
To achieve higher isolation, in the dual TCS application, it is recommended to maintain one Binary Input channel
should not be connected between 110 V DC and 230 V AC control supply.
NOTE:
Use the correct threshold voltages for BI when using TCS with 2 BI.
NOTE:
It is recommended to use Resistor (R), when the low voltage BI is used in the high voltage application. For e.g:
BI44 is used 220 V DC application.
With use of Resistor(R) mentioned above, BI threshold will increase due to voltage drop across external resistor.
© 2018 Siemens Protection Devices Limited
BO
TRIP CCT n FAIL
BI
+ve
-ve
BI
+ve
-ve
BO 1
BO n
Remote
Alarm
Figure 5-8
Trip Circuit Supervision Scheme 3 (H7)
BO
CLOSE CCT n FAIL
BI
+ve
-ve
BO 1
BO n
Remote
Alarm
Figure 5-9
Close Circuit Supervision Scheme
7SR10, 7SR11, 7SR12 Applications Guide
52a
TRIP COIL
Circuit
Breaker
52b
H7 Scheme Notes:
BI =19V DC (48V DC supply)
BI = 44V (110, 220V AC/DC supply)
BI = 88V (220V AC/DC supply)
R = 3K3 typical
52a
CLOSE
COIL
Circuit
R
Breaker
52b
H5 Scheme Notes:
BI =19V DC (24, 48V DC supply)
BI = 44V, 88V (110, 220V AC/DC supply)
R = 3K3 typical
Chapter 7 Page 39 of 41
-
-