3.3
60CTS & 60CTS-I Current Transformer Supervision
3.3.1

Reference

Parameter
I
Current Threshold
thresh
Applied Current
I
(for operate time)
t
Delay setting
d
V
Voltage Threshold
thresh
3.3.2
Current & Voltage Threshold
Attribute
I
CT failed current level
op
Reset level
V
CT failed voltage level
op
Reset level
Repeatability
Variation
3.3.3

Operate and Reset Time

Attribute
t
Basic operate time
basic
Operate time
Repeatability
© 2018 Siemens Protection Devices Limited
Directional Relays have additional VT settings
-10 °C to +60 °C
f
± 5 %
nom
harmonics to f
cutoff
Value
0.05, 0.1... 2xI
Healthy CT
5 x I
Phases
Failed CT phase
0
0.3, 20.00, 20.50... 100, 101...
1000, 1010... 10000, 10100...
14400 s
7, 8... 110 V
Value
100 % I
, ± 5 % or ± 1% I
thresh
90 % I
± 5 % or ± 1% I
op,
100 % V
, ± 2 % or ± 0.5 V
thresh
110 % V
, ± 2 % or ± 0.5 V
op
± 1 %
≤ 5 %
≤ 5 %
Value
50 ms ± 20 ms
t
+ t
, ± 1 % or ± 20 ms
d
basic
± 1 % or ± 20 ms
7SR10 Performance Specification
n
thresh
n
n
Chapter 3 Page 49 of 52