Siemens 7SR10 Argus Series Manual page 133

Overcurrent relay
Table of Contents

Advertisement

Attribute
Reset time
Repeatability
Overshoot time
Disengaging time
Figure 2.12-1and Figure 2.12-4 show the operate and reset curves for the four IEC IDMTL curves with a time
multiplier of 1.
Figure 2.12-2 and Figure 2.12-3 show the ANSI operate and reset curves. These operate times apply to non-
directional characteristics. Where directional control is applied then the directional element operate time should be
added to give total maximum operating time.
© 2018 Siemens Protection Devices Limited
ANSI DECAYING
IEC DECAYING
t
res
Value
R
t
=
×
Tm
, ± 5 % absolute or ± 50 ms,
[ ]
res
2
1
I
Is
for char = ANSI-MI : R = 4.85
ANSI-VI : R = 21.6
ANSI-EI : R = 29.1
R
t
=
×
Tm
, ± 5 % absolute or ± 50 ms,
[ ]
res
2
1
I
Is
for char =
IEC-NI : R = 9.7
IEC-VI : R = 43.2
IEC-EI : R = 58.2
IEC-LTI : R = 80
t
, ± 1 % or ± 20 ms
res
± 1 % or ± 20 ms
< 40 ms
< 50 ms
7SR10 Performance Specification
Chapter 3 Page 35 of 52