Siemens 7SR10 Argus Series Manual page 204

Overcurrent relay
Table of Contents

Advertisement

7SR10 Technical Manual
Double Bit Input Points
Static (Steady-State) Object Number: 3
Change Event Object Number: 4
Static Variation reported when variation 0 requested: 1 (Double Bit Input w/o status)
Change Event Variation reported when variation 0 requested: 1 (Double Bit Input Change w/o Time)
Point
Description
Index
14 User DP Command 5
15 User DP Command 6
16 User DP Command 7
17 User DP Command 8
5.3.3 Binary Output Status Points and Control Relay Output Blocks
The following table lists both the Binary Output Status Points (Object 10) and the Control Relay Output Blocks (Object
12).
While Binary Output Status Points are included here for completeness, they are not often polled by DNP 3.0 Masters.
Binary Output Status points are not recommended to be included in class 0 polls.
As an alternative, it is recommended that "actual" status values of Control Relay Output Block points be looped
around and mapped as Binary Inputs. (The "actual" status value, as opposed to the "commanded" status value, is the
value of the actuated control. For example, a DNP control command may be blocked through hardware or software
mechanisms; in this case, the actual status value would indicate the control failed because of the blocking. Looping
Control Relay Output Block actual status values as Binary Inputs has several advantages:
it allows actual statuses to be included in class 0 polls,
it allows change event reporting of the actual statuses, which is a more efficient and
time-accurate method of communicating control values,
and it allows reporting of time-based information associated with controls, including any
delays before controls are actuated, and any durations if the controls are pulsed.
The default select/control buffer size is large enough to hold 10 of the largest select requests possible.
Binary outputs are by default NOT returned in a class zero interrogation.
Note, not all points listed here apply to all builds of devices.
Binary Output Status Points
Static (Steady-State) Object Number: 10
Change Event Object Number: 11
Control Relay Output Blocks (CROB) Object Number: 12
Binary Output Command Event Object Number: 13
Static Variation reported when variation 0 requested: 1 (Binary Output w/o status)
Change Event Variation reported when variation 0 requested: 1 (Binary Output Event w/o Time)
Command Event Variation reported when variation 0 requested: 1 (Command Status w/o Time)
Point
Description
Index
1 RL 1
Chapter 4 - Page 54 of 78
or 2 (Double Bit Input with status)
or 2 (Double Bit Input Change with Absolute Time)
or 3 (Double Bit Input Change with Relative Time)
Default Change Event
Assigned Class
(1, 2, 3 or none)
0,2
0,2
0,2
0,2
or 2 (Binary Output with status)
or 2 (Binary Output Event with Time)
or 2 (Command Status with Time)
Default
Change
Default
Default
Event
Variation
Variation
Assigned
Static
Event
Class
Object 10
Object 11
(1, 2, 3
or none)
0
2
2
Default Variation
Default Variation
Static Object 3
Event Object 4
1
1
1
1
Default
Command
Default
Event
Variation
CROB
Object 13
Command
Supported
Assigned
Event
Operations
Class
Object 13
(1, 2, 3
or none)
Pulse On
0
1
Latch On
© 2018 Siemens Protection Devices
3
3
3
3
Default
CROB
Operations
Pulse On

Hide quick links:

Advertisement

Table of Contents
loading