5 Installation
• Start the Box PC
• Start applications
• Create a power interruption
• Monitor the shutdown sequence and confirm a correct shutdown sequence
The UPS is connected and configured.
The Box PC will shut down properly in case of a power supply interruption and restart automatically
when the power is restored.
Additional Information
The default Input sensitivity setting is Standard voltage sensitivity and this is correct.
Do not set this parameter to Low voltage sensitivity. Doing so can cause a system malfunc-
tion when switching to battery mode.
5-52
NY-series Industrial Box PC Hardware User's Manual (W553)