Crimp terminals
Use crimp terminals with dimensions X = M4 and Y = 8 mm max.
Y X
5-4-3
Wire the Power Connector
This section describes how to wire the power connector.
Precautions for Safe Use
• Do not perform a dielectric strength test.
• Always use the recommended uninterruptible power supply (UPS) to prevent data loss and
other system file integrity issues caused by unexpected power interruption. Back up the sys-
tem files in the planned way to prevent data loss and other system file integrity issues caused
by incorrect operation.
Additional Information
• The selected conductor size must match with the used maximum power supply capacity or an
overcurrent protection device must be used.
• The used wires and the overcurrent protection device must meet the applicable national
standards.
Standards are:
• NEC (National Electric Code)
• CEC (Canadian Electrical Code)
• international applicable standards
• Refer to 4-1-2 General Electrical Specifications on page 4-3 for electrical specifications.
• Refer to 4-1-3 Power Consumption Specifications on page 4-4 for power consumption specifi-
cations.
• Refer to 3-10-11 UPS on page 3-31 for UPS information.
NY-series Industrial Box PC Hardware User's Manual (W553)