7063-Cr1 Hardware Management Console Specifications - IBM 8408-44E Site And Hardware Planning

Hide thumbs Also See for 8408-44E:
Table of Contents

Advertisement

Table 107. Noise emissions (Maximum configuration)
Acoustical characteristics
L
WAd
1. The noise emission level that is stated is the declared (upper limit) sound power level, in bels, for a random
sample of servers. All measurements are made in accordance with ISO 7779 and reported in conformance with
ISO 9296.

7063-CR1 Hardware Management Console specifications

Hardware specifications for model 7063-CR1 provide detailed information for your Hardware
Management Console (HMC), including dimensions, electrical, power, temperature, environmental
specifications, and noise emissions.
The HMC controls managed systems, including the management of logical partitions and the use of
capacity on demand. Using service applications, the HMC communicates with managed systems to
detect, consolidate, and send information to IBM for analysis. The HMC provides service technicians with
diagnostic information for systems that can operate in a multiple-partitioned environment.
Use the following specifications to plan for your HMC.
Table 108. Dimensions
Width
437 mm (17.2 in.)
1, 2
Table 109. Electrical
Electrical characteristics
Maximum measured power
Maximum kVA
Maximum thermal output
Input voltage
Frequency
1. Preliminary data is subject to change.
2. Power consumption and heat output vary depending on the number and type of optional features that are
installed and the power-management optional features that are in use.
Table 110. Environment requirements
Environment
ASHRAE class
1
Airflow direction
2
Temperature
Humidity range
Maximum rate of change
Maximum dew point
Maximum operating
altitude
82
Site and hardware planning
1
Idling
6.1 bels
Depth
705.3 mm (27.76 in.)
Recommended operating
requirements
18°C - 27°C (64°F - 80°F)
5.5°C (42°F) dew point (DP)
to 60% relative humidity
(RH) and 15°C (59°F) dew
point
Operating
6.1 bels
Height
43.0 mm (1.7 in.)
Properties
300 W
0.330
1024 BTU/hr
100 - 127 V ac or 200 - 240 V ac
50 or 60 Hz
Allowable operating
requirements
A2
Front-to-back
10°C - 35°C (50°F - 95°F)
20% - 80% RH
5°C/20 hrs
21°C (70°F)
3050 m (10000 ft)
Weight
14.5 kg (32 lb)
Nonoperating
requirements
5°C - 45°C (41°F - 113°F)
8% - 80% RH
27°C (80°F)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

8408-e8ePower systems series

Table of Contents