IBM 8408-44E Site And Hardware Planning page 131

Hide thumbs Also See for 8408-44E:
Table of Contents

Advertisement

Table 134. 7196 PDU+ specifications (continued)
Characteristics
Operating temperature at 0 - 914 m (0 - 3000 ft)
(room ambient)
Operating temperature at 914 - 2133 m (3000 -
7000 ft) (room ambient)
Operating humidity
Localized air temperature in PDU
Rated frequency (all feature codes)
Circuit breakers
Power outlet
Figure 52. Wiring diagram for the 7196 PDU+
HVDC PDU
Table 135. HVDC PDU features
PDU Number
EPAA
Properties
10 - 32°C (50 - 90°F)
10 - 35°C (50 - 95°F)
8 - 80% (noncondensing)
60 °C (140 °F) maximum
50 - 60 Hz
Six double-pole branch rated circuit breakers rated at 20 A
Six IEC 320-C19 outlets rated at 16 A (VDE) or 20 A (UL/CSA)
Racks usage
7014-T00, 7014-T42, and 7965-94Y
racks
Supported power cords (PDU to
wall)
Not applicable - fixed power cord
Site and hardware planning
115

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

8408-e8ePower systems series

Table of Contents