Connection and configuration of a 230-V dosing pump for disinfectant
at the disinfection outlet.
The disinfection outlet is valid for any type of disinfection. It is a dry contact and does not supply any voltage.
1 - Connect the cables in accordance with the diagram.
2 –Select AUTO in the sub-menu Disinfectant/Mode so that the dosing pump supplies the
disinfectant until the set value is reached. OFF completely stops the disinfection.
3 – Select in the Disinfectant/Set-point sub-menu the value (in mV, by default 700 mV, see the
bottom of this page) that needs to be reached.
4 - If required, selecting Priming and pressing on Valid. manually starts the connected pump as
long as Valid. remains pressed in.
- Enter the secured Install menu (on the main menu, press Esc and Valid at the same time for
3 secs. A star appears in the top right corner of the home screen).
5 -In the Disinfectant/Type sub-menu, select PUMP to indicate that the disinfection is not done
by an electrolyser.
6 - In the Disinfectant/Stop threshold sub-menu, modify the temperature limit below which the
pump will no longer function, which is 16 °C by default).
7 - In the Disinfectant/Injection sub-menu, modify the duration of each injection (from 1 to
255 secs, by default 15 secs) performed every 15 minutes.
8 - In the pH/Max. volume sub-menu, modify the maximum daily injectable volume (from 0.1 to
9.9 l, by default 0.5 l) for a pump with a flow rate of 1 l/h.
9 - In the Disinfectant/Alert range sub-menu, modify the value of the gap (positive or negative)
for an alert (flashing) to be triggered in relation to the set value. For example, in case of a RedOx
setpoint at 700 mV, with an alert threshold at 100, the RedOx value will flash on the home screen
if it reaches or exceeds 600 mV or 800 mV.
CLASSIC MENU
- M od e: AUTO
S e t- p oint: 70 0 mV
Pr im ing
Additional functions of the instal. menu
INSTAL. MENU
-Mode : AUTO
Set-point : 700mV
Type: PUMP
Stop threshold : 16°C
Injection
: 19s
Max. volume : 0.5L/d
Alert range : 100
Priming
Cl Br
H2O2
Cl
Disinfectant
is
injected
after
filtration,
after
the heat pump
and after the
probes.