Connection of a safety filtration feedback system
To prevent any acid or chlorine being added without any water flow, securing the operation of SOLEO CL
by connecting a flow switch after the filtration pump is necessary. SOLEO CL will only start the pH or
disinfectant control (never at the same time) if the contact of this flow rate detector is closed.
1 - Connect the flow switch to the air temperature inlet in
accordance with the diagram. If this input is already in use
by a temperature probe, connecting the flow switch in
parallel is sufficient.
Secured Install menu (on the main menu, press Esc and
Valid at the same time for 3 secs. A star appears in the top
right corner of the home screen).
2 - In the Filtration menu, go down to Flow Switch and
select: YES.
Use of RedOx
If the amperometric probe is inoperative, if a shock chlorination needs to be performed (risk of damage with freezing
and to the membrane of the amperometric probe) or even in the case of active wintering, relying on the values supplied
by the RedOx probe to guide disinfection is advised.
The RedOx/ORP (oxidation reduction potential) is the disinfectant concentration level (chlorine, bromine, active oxygen,
etc.) present in the pool. Keeping within 650 mV and 750 mV is recommended for this 'disinfection power' measurement.
The oxidation reduction potential indicates the oxidiser quality present in the water. It is the result of the disinfectant
quantity/pollution quantity ratio.
16:03 Water:+26.3°C
Filtration: ON
RedOx: 261mV
Air:+25.0°C pH: 7.2
16
-Fi l t rat i on : O N
St a r t: 07 : 00
Stop: AU TO
M od e : E CO
ORP pr i or i t y : ON
Anti fre e ze : + 3 °C
Eco mod e : -3 0%
Tur bo mod e : + 3 0 %
-Fl ow Sw i tc h : YE S
A RedOx WHICH IS TOO HIGH IRRITATES SKIN AND MAY
DAMAGE PARTS OF YOUR POOL. A RedOx WHICH IS TOO
LOW MAY BE A HYGIENE HAZARD
> ensure that: the canister has been removed from the
RedOx probe (see p04) and that the RedOx probe is not
clogged (see p23)
> manual regulation (OFF position): > Add the disinfectant
(chlorine, bromine, active oxygen, etc.) until the desired
value is reached.