Memory Allocation
I/O
Address
Word
Input
n+7
n+8 Loop 1
n+9 Loop 2 14
9 L
2
Data item
Bit
15 to 12
Loop 1
executed
bank
number
11 to 08
Loop 2
executed
bank
number
07 to 02
---
01
SW2-2
00
SW2-1
15
---
Sensor
error
13 to 10
---
09
MAN
08
RUN
07 to 05
---
04
Control
output
03
AT
02
---
01
AL1
00
AL2
Data contents
Outputs the bank number currently executed for Loop 1 and Loop
2 as 1-digit BCD data.
Not used. Each bit is set to 0.
Outputs the ON/OFF status of SW2-2 (setting direction).
0: Data Setting Console
1: C200H PC
Outputs the ON/OFF status of SW2-1 (switching memory
contents).
0: Fixed
1: Normal
Not used. Set to 0.
Bit set to 1 if an input is not connected, an input wire
is broken, or the input data exceeds the operational
range.
Not used. Each bit is set to 0.
ON (set to 1) for Manual Output Mode.
ON (set to 1) during operation.
Not used. Each bit is set to 0.
Bit set to 1 when the control output (transistor or
voltage output) is ON.
Bit set to 1 during auto-tuning (AT).
Not used. Set to 0.
Bit set to 1 when the value enters the set alarm
range (Refer to page 23).
(R f
23)
Section 4-1
Loop 1/2
status data
d
39