Memory Allocation
I/O
Address
Word
Input
n+3
n+4
n+5
n+6
n+7
n+8 Loop 1
n+9 Loop 2
SW2-1 in Normal Position
I/O
Address
Word
Output
n
Data item
Bit
15 to 00
Loop 1 PV
15 to 00
Loop 2 PV
15 to 00
Loop 1 SP
15 to 00
Loop 2 SP
15 to 12
Loop 1
executed
bank
number
11 to 08
Loop 2
executed
bank
number
07 to 02
---
01
SW2-2
00
SW2-1
15
---
14
Sensor
error
13 to 10
---
09
MAN
08
RUN
07 to 05
---
04
Control
output
03
AT
02
---
01
AL1
00
AL2
Data item
Bit
15 and 14
Read/Write The data bit sets operation to read or write.
13 and 12
Loop no.
11 to 08
Bank no.
07 to 00
Command
Data contents
Outputs the Loop 1 and Loop 2 PV (process value) as 4-digit
BCD data. The most significant digit is F for minus (–).
g
Outputs the Loop 1 and Loop 2 SP (set point) as 4-digit BCD
data. The most significant digit is F for minus (–).
d
Th
i
ifi
di i i F f
Outputs the bank number currently executed for Loop 1 and Loop
2 as 1-digit BCD data.
Not used. Each bit is set to 0.
Outputs the ON/OFF status of SW2-2 (setting direction).
0: Data Setting Console
1: C200H PC
Outputs the ON/OFF status of SW2-1 (switching memory
contents).
0: Fixed
1: Normal
Not used. Set to 0.
Bit set to 1 if the sensor is not connected, a sensor
wire is broken, or the input data exceeds the
operational temperature range.
Not used. Each bit is set to 0.
ON (set to 1) for Manual Output Mode.
ON (set to 1) during operation.
Not used. Each bit is set to 0.
Bit set to 1 when the control output (transistor or
voltage output) is ON.
Bit set to 1 during auto-tuning (AT).
Not used. Set to 0.
Bit set to 1 when the value enters the set alarm
range. (Refer to page 23.)
(R f
23 )
Data contents
Write = 01 Read = 00
The data bit sets the Loop Number to which the
read or write operation applies.
Loop 1 = 01, Loop 2 = 10
Sets the bank number to which the read or write
operation applies as 1-digit BCD data. Set executed
bank numbers from 1 to 8.
Sets the command code (Refer to page 40) for the
read or write operation as 2-digit BCD data.
Section 4-1
g
( )
(
)
g
i
( )
Loop 1/2
status data
(n=100 + 10 x Unit number)
Read/Write
command
37