Memory Contents - Omron C200H-PID01 Operation Manual

Pid control unit
Hide thumbs Also See for C200H-PID01:
Table of Contents

Advertisement

Memory Allocation
I/O
I/O
Word
Word
15
14
Input
n+4
Loop 2 PV (see note)
0 to 9, F
n+5
Read data (see note)
0 to 9, F
n+6
0
Loop 1 executed bank
n+7
number
b
n+8
Loop 1 status data
0
Sen-
sor
error
n+9
Loop 2 status data
0
Sen-
sor
error

4-1-2 Memory Contents

SW2-1 in Fixed Position
I/O
Address
Word
Output
n
n+1
n+2
36
13
12
11
10
0 to 9
0 to 9
Write
0
error
Loop 2 executed bank
number
b
0
0
0
0
0
0
Note Four digits BCD and the decimal point position are designated by the "decimal
point position" parameter. The most significant digit (F) = minus (–).
Data item
Bit
15 to 00
Loop 1 SP
15 to 00
Loop 2 SP
15 to 12
Loop 1
executed
bank
number
11 to 08
Loop 2
executed
bank
number
07
Loop 1
MAN
06
Loop 1
RUN
05
Loop 2
MAN
04
Loop 2
RUN
03 to 00
---
Bit
09
08
07
06
0 to 9
0 to 9
0
Write
0
com-
plete
0
RUN
0
0
MAN
RUN
0
0
MAN
Data contents
Sets the Loop 1 and Loop 2 SP (set point) as 4-digit BCD data.
Set the most significant digit to F for minus (–).
Note These specified values apply to the bank number set with Wd
Note These specified values apply to the bank number set with Wd
(n+2) and can are written directly to RAM. (Refer to 4-3 Pro-
gramming. )
Sets the bank number executed for Loop 1 and Loop 2 as 1-digit
BCD data. Set executed bank numbers from 1 to 8. If the value is
set out of this range, the bank number reverts to the previous
value.
a ue
This is the Loop 1 Manual Output Mode bit. When it is set to 1,
the Unit goes into Manual Output Mode.
This is the Loop 1 Run/Stop bit. When it is set to 1, operation
starts; when it is set to 0, operation stops.
This is the Loop 2 Manual Output Mode bit. When it is set to 1,
the Unit goes into Manual Output Mode.
This is the Loop 2 Run/Stop bit. When it is set to 1, operation
starts; when it is set to 0, operation stops.
Not used. Set to 0.
Section 4-1
05
04
03
02
01
0 to 9
0 to 9
0
0
0
0
0
SW2
2
0
Con-
AT
0
AL1 AL2
trol
out-
put
0
Con-
AT
0
AL1 AL2
trol
out-
put
(n=100 + 10 x Unit number)
00
Read
com-
plete
1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac c200h-pid0 seriesC200h-pid02C200h-pid03Sysmac c200h-pid01Sysmac c200h-pid03Sysmac c200h-pid02

Table of Contents