Parameter Displays and Settings
Input-type Monitor (Display Level 2)
Alarm 1 and Alarm 2 Modes (Display Level 2)
PV
SV
Note Cannot be set.
PV
SV
PV
SV
Select the desired alarm type from the following chart and set the number (X: set
value)
ALARM
mode
0
No alarm
1
Upper- and lower-limit alarm
2
Upper-limit alarm
3
Lower-limit alarm
4
Upper- and lower-limit range alarm
5
Upper- and lower-limit alarm with
standby sequence
6
Upper-limit alarm with standby
sequence
7
Lower-limit alarm with standby
sequence
8
Absolute-value upper-limit alarm
9
Absolute-value lower-limit alarm
Standby Sequence
When the power is turned on, the value is below the set point, so alarm output
status occurs with regard to the lower limit alarm. In this situation, if "lower limit
Input-type monitor parameter symbol
SW202 set value
Alarm 1 Mode parameter symbol
Alarm 1 Mode of currently selected loop
Alarm 2 Mode parameter symbol
Alarm 2 Mode of currently selected loop
Alarm Type
Section 3-4
Alarm Range
0
SP
x
x
x
x
x
x
x
x
x
x
x
x
31