York HIDS006B21S Service Manual page 67

Inverter-driven multi-split system heat pump air conditioners
Table of Contents

Advertisement

Other
Abnormalities
Event
"Motion Sensor
is activated" is
indicated on Wired
Controller LCD.
Operation Stops
though Someone is
Present.
Not Operating
in "Avoid Air" or
"Receive" though
Someone is
Present.
Operation Continues
though No One is
Present.
Operating in "Avoid
Air" or "Receive"
though No One is
Present.
"Radiation Sensor is
activated" is indicated
on Wired Controller
LCD.
SM-18001-rev.1
(Motion and Radiation Sensor)
Cause
Reaction rate is always
100%.
Reaction rate is always
0%.
Motion sensor setting
is disabled on the wired
controller.
Motion sensor setting
of No presence is set to
other than "Stop" on the
wired controller.
There are heat source
other than human in the
detecting area of the
sensor.
There is sensor with high
sensitivity.
Operating in "Avoid Air" or "Receive".
15 minutes has not
passed since someone
left the room.
There are heat sources
other than human in the
detection area of the
sensor.
Radiation sensor element
is abnormal.
Abnormalities of Devices
Check Item
Check the "Check Mode 1:
q1" on the wired controller.
Check if there is motion
sensor with "Reaction rate
always 100%".
Operate under detection
area of motion sensor and
check the "Check Mode 1:
q1" on the wired controller.
Check if there are motion
sensors with "Reaction
rate always 0%".
Check setting on the wired
controller.
Check setting on the wired
controller.
Check heat source
(a moving object whose
temperature is different
from surroundings).
Stop the operation from the
wired controller, no motion
in the detection area of the
motion sensor and check
the "Check Mode 1: q1".
Check if there is no motion
sensor with "Reaction rate
0%".
Check the louver operation
after no one has been in
the room for more than 15
minutes.
Check heat source
(a moving object whose
temperature is different
from surroundings).
TROUBLESHOOTING
Action
(Turn OFF Main Switch)
True: Replace motion
and radiation sensors
PCB.
False: Replace control
PCB.
True: Replace motion
and radiation sensors
PCB.
False: Sensitivity may
be low. Adjust the
[Optional Function: K6]
to [01: High Sensitivity]
and see if there are any
changes. If the symptom
continues, replace
motion and radiation
sensors PCB.
Correct the setting.
Correct the setting.
Remove it.
True: Replace motion
and radiation sensors
PCB.
False: No problem.
Adjust the [Optional
Function: K6] to [02: Low
Sensitivity] and see if
there are any changes. If
the symptom continues,
replace motion and
radiation sensors PCB.
Not operating in "Avoid
Air" or "Receive". This is
normal operation.
Remove it.
Replace motion and
radiation sensors PCB.
3-45

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents