INSTALLATION INSTRUCTION

GENERAL
These condensing units are designed for outdoor installation
on a roof or at ground level. Every unit is completely piped and
wired at the factory and is shipped ready for immediate instal-
lation. Only the liquid and suction lines to the evaporator coil,
the filter drier, the control wiring and the main power wiring are
required to complete the installation. Each unit is dehydrated,
evacuated, leak tested and pressure tested at 450 psig before
being pressurized with a holding charge of refrigerant-22 for
shipment and/or storage.
All controls are located in the front of the unit and are readily
accessible for maintenance, adjustment and service. All wiring
(power and control) can be made through the front of the unit.
REFERENCE
This instruction covers the installation and operation of the
basic condensing unit. For information on the installation and
operation of the evaporator blower units, refer to instruction
Form 550.23-N4Y.
Installer should pay particular attention to the words: NOTE, CAUTION and WARNING . Notes are intended to clarify or make
the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury
and/or equipment damage may result if installation procedure is not handled properly.
CONDENSING UNITS
Supersedes: 550.23-N6Y (398)
MODELS H3CE180 & 240
All accessories come with a separate Installation Manual.
Refer to Parts Manual for complete listing of replacement parts
on this equipment.
All forms may be ordered from:
INSPECTION
As soon as a unit is received, it should be inspected for possible
damage during transit. If damage is evident, the extent of the
damage should be noted on the carrier's freight bill. A separate
request for inspection by the carrier's agent should be made in
writing.
SPLIT-SYSTEM

(AIR COOLED)

Publications Distribution Center
Unitary Products Group
P.O. Box 1592, York, Pa. 17405
550.23-N6Y (998)
035-15470

Advertisement

Table of Contents
loading

Summary of Contents for York H3CE180

  • Page 1: Air Cooled

    Unitary Products Group shipment and/or storage. P.O. Box 1592, York, Pa. 17405 All controls are located in the front of the unit and are readily accessible for maintenance, adjustment and service. All wiring INSPECTION (power and control) can be made through the front of the unit.
  • Page 2: Table Of Contents

    550.23-N6Y TABLE OF CONTENTS General ................1 Compressor Control Module..........11 Reference................1 Low or High Pressure Lock Out Operation......11 Inspection................1 Resetting the Lock Out ............12 Nomenclature............... 2 Second Stage of Cooling ........... 12 Low Ambient Cooling............12 INSTALLATION Safety Features..............
  • Page 3: Installation

    550.23-N6Y INSTALLATION GROUND LEVEL LOCATIONS LIMITATIONS These units must be installed in accordance with all national The units must be installed on a one-piece level concrete slab and local safety codes. If no local codes apply, installation must with a minimum thickness of 4 inches. The length and width conform with the appropriate national codes.
  • Page 4: Clearances

    Holding charge is the amount in the unit as shipped from the factory. Operating refrigerant charge is for the condensing unit and the matching York air handler, but does not include the charge in the interconnecting piping. See the Refrigerant Line Charge Table to determine the additional refrigerant charge required for interconnecting piping.
  • Page 5: Electrical Data

    550.23-N6Y FIG. 3 - TYPICAL FIELD WIRING TABLE 3 - ELECTRICAL DATA Compressor Condenser Fan Motor Unit Maximum Minimum Minimum Unit Power Circuit Fuse Disconnect Model Supply Ampacity Size Size (Amps) (Amps) (Amps) H3CE150A50 380/415 27.8 1/.75 2.2/2.0 35.7 H2CE180A50 380/415 36.8 1/.75...
  • Page 6: Point Loads

    550.23-N6Y All dimensions are in inches. They are sub- ject to change without notice. Certified di- Connection Size Connection mensions will be provided upon request. Entry 15 Ton 20 Ton CLEARANCES Suction Line 1-5/8 ID 2-1/8 ID Overhead (Top) 120" Liquid Line 5/8 OD 5/8 OD...
  • Page 7: Refrigerant Piping

    550.23-N6Y REFRIGERANT PIPING LINE SIZING GENERAL GUIDELINES When sizing refrigerant lines for a split-system air conditioner, check the following: Many service problems can be avoided by taking adequate pre- 1. Suction line pressure drop due to friction at full capacity, cautions to provide an internally clean and dry system and by using 2.
  • Page 8: Liquid Lines

    550.23-N6Y TABLE 5 - LIQUID LINES Pressure Drop Nominal Refrigerant Type L Model Vertical Capacity Flow Rate Copper Tubing Friction Designation Rise (Tons) (Lbs./Min.) (Inches O.D.) (PSI/100 Ft.) (PSI/Ft.) 180 Mbh 240 Mbh 1Based on Refrigerant-22 at the nominal capacity of the condensing unit, a liquid temperature of 105°F and a suction temperature of 40°F. These friction losses do not include any allowances for a strainer, filter-drier, solenoid valve, isolation valve or fittings.
  • Page 9: Installation

    550.23-N6Y EXTENDING THE SERVICE PORTS 3. Unbraze the coil’s liquid line disc while maintaining a flow of dry nitrogen across the connection and through the hole (see Fig. 6) in the liquid line disc. 1. Loosen the screws that secure the service ports in shipping NOTE: If the liquid line has a solenoid valve, the valve position.
  • Page 10: Extending The Service Ports

    550.23-N6Y Alternate Charging Methods Method 2: Install a field supplied moisture indicating sight glass in the liquid line between the filter-drier and If you are starting a unit when the ambient temperature is higher the evaporator coil. or lower than those shown in Fig. 7, either of the following methods may be used.
  • Page 11: Charging Curve For Hce180

    550.23-N6Y Charging Curve H*CE180 115°F Ambient 105°F Ambient 95°F Ambient 85°F Ambient 75°F Ambient Suction Pressure FIG. 7 - CHARGING CURVE FOR HCE180 Charging Curve H*CE240 115°F Ambient 105°F Ambient 95°F Ambient 85°F Ambient 75°F Ambient Suction Pressure FIG. 8 CHARGING CURVE FOR HCE240 Unitary Products Group...
  • Page 12: Start-Up

    HP is open. temperature falls below 50 F and closes as the ambient rises above 60 F. TLA is used on the H3CE180, not the H3CE240. Once the LOR coil has been energized, it remains energized,...
  • Page 13: Resetting The Lock Out

    COMPRESSOR REPLACEMENT Contact the local UPG Distribution Center for compressor or parts. P .O. Box 1592, York, Pennsylvania USA 17405-1592 Subject to change without notice. Printed in U.S.A Copyright © by York International Corporation 1998. All Rights Reserved. 550.23-N6Y Code: SBY...

This manual is also suitable for:

H3ce240

Table of Contents