Picking Up Operation Signal - York HIDS006B21S Service Manual

Inverter-driven multi-split system heat pump air conditioners
Table of Contents

Advertisement

EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
5.4.1.6 Picking Up Operation Signal
Up to 3 of the following 7 signals can be picked up by setting this function to CN7 and CN8
the following figures. Make sure to use a field-supplied remote control adopter PSC-5RA for picking up
signals. The wiring length shall be 230 ft. (70m) or less. The settings for picking up signals (1), (2) and (4)
are already set at the factory.
NOTE:
1. Output terminal (CN8) is no longer available for Ducted Medium Static type and Ducted Slim type indoor
units produced in April 2018 or later.
(1) Picking Up Operation Signal [ Output Setting: Code (01) ]
This function is utilized to pick up an operation signal that has nothing to do with the compressor
stoppage by a thermistor. An example of basic wiring is shown below. The contact of the auxiliary
relay "RYa" is closed when this operation signal is given. This function enables the signal check during
remote control operation and an interlock of the fan for air inlet, etc. The contact of the auxiliary relay
"RYa" is opened while the protection devices are activated.
(2) Picking Up Alarm Signal [ Output Setting: Code (02) ]
This signal is utilized to pick up an alarm signal while safety devices are activated. However, this
function is not available during abnormal communication of the wired controller. An example of basic
wiring is shown below. The contact of the auxiliary relay "RYa" is closed while the protection devices
are activated.
5-14
CN7 Connector
CN7
2
1
3 P Connector

Picking Up Operation Signal

(Example: Operation Output is set to terminals 1 and 2 of CN7.)
CN7 Connector
CN7
3
1
3 P Connector
Picking Up Alarm Signal
(Example: Alarm Output is set to terminals 1 and 3 of CN7.)
Indoor Unit PCB
Auxiliary Relay
RYa
RY
Indoor Unit PCB
Auxiliary Relay
RYa
RY
1
according to
SM-18001-rev.1