York HIDS006B21S Service Manual page 33

Inverter-driven multi-split system heat pump air conditioners
Table of Contents

Advertisement

Features of Check Mode 1
No.
Item
1
b1
Set Temp.
2
b2
Inlet Air Temp.
3
b3
Discharge Air Temp.
4
b4
Liquid Pipe Temp.
5
b5
Remote Thermistor Temp.
6
b6
Outdoor Air Temp.
7
b7
Gas Pipe Temp.
8
b8
Evaporating Temp. at Heating
9
b9
Condensing Temp. at Cooling
10
bA
Comp. Top Temp.
11
bb
Thermo Temp. of Wired Controller
12
bC
Not Prepared
13
C1
I.U. Micro-Computer *
14
C2
O.U. Micro-Computer *
15
d1
Stopping Cause State Indication
16
E1
Times of Abnormality
17
E2
Times of Power Failure
18
E3
Times of Abnormal Transmitting
19
E4
Times of Inverter Tripping
20
F1
Louver Sensor State
21
H1
Discharge Pressure
1
*
The average value for 30 seconds (update cycle time of Check Mode) is displayed on the LCD.
2
*
"C1" and "C2" are indicated by digital number like a 7-segment display.
Each signal means state of following item. (When ON, signal is displayed)
2
3
1
4
5
Features of Check Mode 2
No.
Item
1
q1
Inlet Air Temp.
2
q2
Discharge Air Temp.
3
q3
Liquid Pipe Temp.
4
q4
Outdoor Air Temp.
5
q5
Gas Pipe Temp.
6
q6
Evaporating Temp. at Heating
7
q7
Condensing Temp. at Cooling
8
q8
Comp. Top Temp.
SM-18001-rev.1
Data Name
2
2
"C1" I.U. Micro-Computer State
1
Operation
2
Alarm
7
3
Heating Thermo ON
4
Cooling Thermo ON
6
5
6
Auxiliary Heater
7
Drain-Up Mechanism
NOTE:
Items for O.U. are different by O.U. model.
For details, refer to the Service Manual for Outdoor Unit.
Data Name
No.
Item
22
H2
Suction Pressure
23
H3
Control Information
24
H4
Operating Frequency
25
J1
I.U. Capacity
26
J2
O.U. Code
27
J3
System Number (1)
28
J4
System Number (2)
29
L1
I.U. Electronic Expansion Valve
30
L2
O.U. Electronic Expansion Valve 1
31
L3
O.U. Electronic Expansion Valve 2
32
L4
O.U. Electronic Expansion Valve B
33
P1
Comp. Current
34
P2
Comp. Operating Accumulated Time
35
q1
Motion Sensor Reaction Rate *
36
q2
Radiation Sensor Temp. *
37
q3
Motion Sensor 1 Reaction Rate *
38
q4
Motion Sensor 2 Reaction Rate *
39
q5
Motion Sensor 3 Reaction Rate *
40
q6
Motion Sensor 4 Reaction Rate *
41
q7
Setting Temp. Collected Value
"C2" O.U. Micro-Computer State
CMC1
RVR1
CMC2
RVR2
-
Outdoor Fan
SVA
SVB
No.
Item
9
q9
Discharge Pressure
10
qA
Suction Pressure
11
qb
Control Information
12
qC
Operating Frequency
13
qd
I.U. Expansion Valve
14
qE
O.U. Expansion Valve 1
15
qF
Comp. Current
TROUBLESHOOTING