York HIDS006B21S Service Manual page 51

Inverter-driven multi-split system heat pump air conditioners
Table of Contents

Advertisement

Alarm
Code
l The RUN indicator (red) flashes.
l The indoor unit number (refrigerant cycle number - address number), the alarm code, the model code
1
the model name
number and the alarm code are displayed on the 7-segment display of the outdoor unit PCB.
Note 1: Except for some models.
This alarm code is displayed when a short (0.24kΩ or less) or open sensor (840kΩ or more) is detected
during a heating or cooling operation. The operation automatically restarts when the malfunction is
removed.
Is thermistor THM5
(for gas pipe) connected
to THM5 of I.U. PCB?
Yes
Is resistance of THM5
between 0.24kΩ and
840kΩ?
Yes
Failure of I.U. PCB
Medium Static Type: (H,Y,C)IDM006 to 048B21S
Event
Failure of
Thermistor
for Indoor Unit
Heat Exchanger
Gas Pipe Temp.
Failure of I.U. PCB
1: The heating operation is available only during the test run.
SM-18001-rev.1
Abnormality of Thermistor for Gas Refrigerant Pipe Temperature
at Indoor Unit Heat Exchanger (Gas Pipe Thermistor)
and the number of connected indoor units are displayed on the LCD. The indoor unit
No
Connect them.
No
Failure of
Thermistor
Refer to "Alarm Code 11"
for thermistor resistance.
Cause
Failure
Incorrect Connection
High Static Type: (H,Y)IDH018 to 048B21S
Slim Type: (H,Y,C)IDS006 to 018B21S
Thermistor for Indoor Heat
Exchanger Gas Pipe
Temperature
Check Item
Check resistance.
Check wiring to
I.U. PCB.
Replace I.U. PCB
and check operation.
TROUBLESHOOTING
1
,
Thermistor for Indoor Heat
Exchanger Gas Pipe
Temperature
Thermistor for Indoor Heat
Exchanger Gas Pipe
Temperature
Action
(Turn OFF Main Switch)
Replace thermistor
if faulty.
Correctly connect wires.
Replace I.U. PCB
if faulty.
3-29