York HIDS006B21S Service Manual page 37

Inverter-driven multi-split system heat pump air conditioners
Table of Contents

Advertisement

(9) No Function
This function is not used.
Press "OK" to proceed.
(10) Communication (Transmission) Circuit Test
The wired controller automatically starts to check
the communication circuit.
(11) Wired Controller Thermistor Test
The detected temperature by the wired controller
thermistor is displayed at "
right.
(12) Date/Time Test
The date and time is changed from "2012.03.04
12:34" to "2008. 01. 01 00:00".
(13) EEPROM Test
< EEPROM Clearing Cancel >
Press "?" (help).
< EEPROM Clear >
Press "OK" or wait 15 seconds. EEPROM data
is cleared. During the process, the numbers
indicate the location with "
If
A
has a value of "999", EEPROM is in a faulty
condition.
*If "
A
" has "999", the process does not proceed
to the next step.
EEPROM Process
(14) Clear EEPROM
The wired controller automatically starts the
EEPROM clearing process.
(15) After several seconds pass, the self checking is completed and the wired controller is automatically
restarted.
SM-18001-rev.1
A
" in the figure at the
A
".
07: No Function
08: Transmission Test
Self Checking
0 7 : 0 0 0
Self Checking
0 9 : 0 2 5
Self Checking
1 0 : 0 0 0
2008.01.01 00:00
Self Checking
1 1 : 0 0 0
Self Checking
1 3 : 0 0 0
TROUBLESHOOTING
A
A
3-15