York HIDS006B21S Service Manual page 56

Inverter-driven multi-split system heat pump air conditioners
Table of Contents

Advertisement

TROUBLESHOOTING
Alarm
Code
l The RUN indicator (red) flashes.
l The indoor unit number (refrigerant cycle number - address number), the alarm code, the model code
the model name
number and the alarm code are displayed on the 7-segment display of the outdoor unit PCB.
Note 1: Except for some models.
This alarm code is displayed in the following condition. Check the unit model code setting (DSW4) of I.U.
PCB after turning OFF the power supply.
The unit model code setting (DSW4) is not set (all pins
are "OFF"), or is set for the incorrect indoor unit type.
Alarm
Code
l The RUN indicator (red) flashes.
l The indoor unit number (refrigerant cycle number - address number), the alarm code, the model code
the model name
number and the alarm code are displayed on the 7-segment display of the outdoor unit PCB.
Note 1: Except for some models.
This alarm code is displayed in the following condition. Check the settings of the DIP switch (DSW) and the
rotary switch (RSW) after turning OFF the power supply.
The unit No. setting (DSW6 and RSW1) or the
refrigerant cycle No. setting (DSW5 and RSW2)
is set as "64" or more, or more than 2 pins of
DSW5 or DSW6 are set.
3-34
Incorrect Setting of Unit Model Code
1
and the number of connected indoor units are displayed on the LCD. The indoor unit
Condition
Incorrect Setting of Unit and Refrigerant Cycle Number
1
and the number of connected indoor units are displayed on the LCD. The indoor unit
Condition
Set DSW4 correctly according to the DIP
switch setting in "Installation and Maintenance
Manual".
Action
a) Unit No. Setting / Ref. Cycle No. Setting Starting
from "1" (recommended)
Set the unit No. and the refrigerant cycle No. from "1"
to "63". (Setting No. for the 64th unit is "0".)
b) Unit No. Setting / Ref. Cycle No. Setting Starting
from "0"
Set the unit No. and the refrigerant cycle No. from "0"
to "63." (Setting No. for the 64th unit is "63".)
Action
SM-18001-rev.1
1
,
1
,

Hide quick links:

Advertisement

Table of Contents
loading