Tests
3.2 Function test
Test procedure
1. The drive is switched on.
2. The drive is switched off and grounded according to the following scheme.
3. The drive is switched off and grounded, the doors are open.
Result
The test is passed if the corresponding switching states occur.
3.2.19

Failure of a power semiconductor module

Fundamentals
The power section must shut down if a power semiconductor module fails. The failure is
simulated by withdrawing the fiber-optic cable connector from the gating module of a power
semiconductor module. This interrupts the control.
Test procedure
1. The auxiliary voltage is present.
2. The fiber-optic cable connector of a gating module is withdrawn.
SINAMICS PERFECT HARMONY GH180 6SR41 F03 F04 F06 F14 F28 F48 F68 F72 F79 G21 K20 K21 K29 L29 L50 L55 L81 L82 L95 M61
30
Action
Initial state with the drive switched on
Drive off
Medium voltage off
Wait 600 s
Local-remote switch off and actuate Emer‐
gency Off
Connect grounding switches -Q1 / Q2
Open the doors
Action
Initial state with the drive switched off
Close the doors
Open grounding switches -Q1 / Q2
Local-remote switch to "Local" and re‐
lease Emergency Off
Medium voltage on
Drive on
A message is displayed on the test station computer.
Switching states
-Q1 / Q2
-K21
-K22
off
off
off
off
off
off
off
off
off
off
on
on
on
on
Switching states
-Q1 / Q2
-K21
-K22
on
on
on
on
off
off
off
off
off
off
off
off
Reference Manual Rev.201902141441 GH180
-K41
-K51
off
on
on
off
on
on
off
on
on
off
on
on
on
off
on
on
off
on
on
off
off
-K41
-K51
on
off
off
on
off
on
on
off
on
off
on
on
off
on
on
off
on
on
N30 N35 N44 N75 M08 U10 Y15