Siemens SIMATIC S7 F Manual page 261

Systems
Table of Contents

Advertisement

Fail-Safe Blocks
Name
SHUTDOWN
RQ_FULL
F_PRG_SIG
ALARM_EN
Outputs:
FULL_SD
EN_INIT
SAFE_M
MSG_ERR
MSG_STAT
MSG_ACK
NFY_DONE
NFY_ERR
Fail-Safe Systems
A5E00085588-03
Data Type
Explanation
BOOL
Defines the response to a
detected FAILURE (rising
edge). Either a "Partial
(isolated F Run-time groups
shutdown) or "Full (entire
Safety Program shutdown).
BOOL
Manual request for entire
Safety Program shutdown. A
rising edge will force a full
shutdown. User may connect
external logic to this input.
DWORD
Safety Program Overall
Signature (created during
compile only – not updated
online)
BOOL
Alarm messaging enabled
allows messages to be
reported to the HMI (WINCC).
The messages (incoming and
outgoing) reported are Full
Shutdown, Partial Shutdown,
Restart of Shutdown Logic,
and Safety Mode (enabled or
disabled).
BOOL
Entire Safety Program
shutdown when TRUE.
Latched output resettable
through RESTART input.
BOOL
Required for Safety Program
initialization logic.
Immediately following the
RESTART request, EN_INIT
will remain TRUE while the
function block initialization
logic executes.
BOOL
Indication of the current
system mode of operation.
1=Safety Mode, 0=Test Mode.
This output may be connected
to external logic.
BOOL
Return of SFB 34 ALARM_8
ERROR output.
WORD
Return of SFB 34 ALARM_8
STATUS output.
WORD
Return of SFB 34 ALARM_8
ACK output.
BOOL
Return of SFB 31 NOTIFY_8P
DONE output.
BOOL
Return of SFB 31 NOTIFY_8P
ERROR output.
Default
Full (1)
0
0
1
0
0
0
0
W#16#0000
W#16#0000
0
0
8-73

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7 fh

Table of Contents