Configuration
4.8

Setting up, Modifying and Cancelling Access Rights

4.8.1

Setting up Access Rights for the CPU

To set up access rights for the CPU, proceed as follows:
1. Select the CPU or its S7 program in SIMATIC Manager.
2. Choose the PLC > Access Rights > Setup menu command. In the dialog
tab box that appears, locate the protection tab and enter the password
assigned during parameter assignment of the CPU.
Access rights are valid until they are canceled (PLC > Access Rights > Cancel)
or until the last S7 application has been terminated.
Safety Note – Limiting Access through ES
!
If access to the ES or programming device is not limited by means of access
protection to those individuals authorized to modify Safety Programs, the efficacy
of the password protection must be ensured by means of the following
organizational measures on the ES/programming device:
The password must only be accessible to people with authorization.
People with authorization must explicitly cancel the authorization when they
exit the ES/programming device. If this is not rigorously adhered to, a screen
saver with a password accessible only to authorized people must also be used.
When the standard program is changed in safety mode, access rights should not
be obtained using the CPU password because otherwise the Safety Program can
also be changed. The protection level must instead be set accordingly.
After access rights have been canceled, check, if safety mode is active, whether
the overall signature of the Safety Program online and the overall signature of the
accepted Safety Program are identical. If not, download the correct Safety
Program to the CPU again (see sections "Downloading Changes" and "Comparing
Safety Programs".
Safety Note – Password Protection
!
After an unbuffered cold restart, the current password is deleted from the RAM
load memory and the old password from the flash EPROM memory card is valid
again. To prevent this old password on the flash EPROM memory card being
known to too many people, you should take organizational measures.
4-8
Fail-Safe Systems
A5E00085588-03