Advertisement

Fail-Safe Blocks
Outputs:
Addressing
You must assign the symbol of the corresponding analog input channel to the input
VALUE of the F channel driver.
Fail-Safe Systems
A5E00085588-03
Name
Data Type Explanation
SIM_ON
F_BOOL
SUBS_ON
F_BOOL
SUBS_V
F_REAL
PASS_ON
F_BOOL
ACK_NEC
F_BOOL
ACK_REI
F_BOOL
PASS_OUT
F_BOOL
QCHF_HL
F_BOOL
QCHF_LL
F_BOOL
QBAD
F_BOOL
QSIM
F_BOOL
QSUBS
F_BOOL
OVHRANGE
F_REAL
OVLRANGE
F_REAL
V
F_REAL
V_DATA
REAL
QUALITY
BYTE
ACK_REQ
BOOL
1= activate simulation value
0= deactivate simulation value
1=enable value substitution
Substitute value
1= activate passivation
0= deactivate passivation
User acknowledgment for
reintegration after error
1 = required
0 = not required
Reintegration acknowledgment
Passivation output
1=input value in overrange
1=input value in underrange
1=process value invalid
1=simulation active
1=value substitution active
Upper limit of the process value
(copy)
Lower limit of the process value
(copy)
Process value
DATA process value
Value status (quality code) of the
process value
Acknowledgment required for
reintegration
Default
0
0
0.0
0
0
0
0
0
0
0
0
0
0.0
0.0
0.0
0.0
0
0
8-17