F_Sendr - Siemens SIMATIC S7 F Manual

Systems
Table of Contents

Advertisement

Fail-Safe Blocks
8.3.3

F_SENDR

Function
This block safely sends 20 data items of the F_REAL data type to another CPU. It
can be received there by the F_RCVR block.
The data to be sent (e.g. outputs from other blocks) is stored at the inputs
SD_R_xx.
The data is transferred via safety frames.
If you want to temporarily switch off a data interchange that has been established
between two CPUs in order to reduce the load on the bus, you can assign the
value 0 to the input EN_SEND. In this case, no more data is sent to the recipient,
and the recipient outputs the configured substitute values. If communication
between the connection partners was already established, when data interchange
restarted with EN_SEND = 1, an acknowledgment is required on the recipient's
side before the values sent are output again.
Startup Characteristics
After a startup (cold restart or warm restart), communication must first be
established between the communication partners. The F_SENDR signals this at
the SUBS_ON parameter with "1". The recipient (F_RCVR) outputs substitute
values during this time until communication between F_SENDR and F_RCVR via
the safety frame has started up and any acknowledgment required for reintegration
at F_RCVR has been made.
I/Os
Name
Inputs:
EN_SEND
ID
R_ID
SD_R_00
...
SD_R_19
TIMEOUT
CRC_IMP
Outputs:
ERROR
SUBS_ON
RETVAL
Fail-Safe Systems
A5E00085588-03
Data Type
Explanation
BOOL
1 = switch transmission on
0 = switch transmission off
WORD
ID addressing parameter
DWORD
R_ID addressing parameter
F_REAL
Send date 00
...
F_REAL
Send date 19
F_TIME
Monitoring time in ms for vital-
sign monitoring
DWORD
Address reference CRC
F_BOOL
Transmission error
F_BOOL
Recipient outputs substitute
values
WORD
Error code
Default
1
0000
00000000
0
0
T#0 ms
Supplied
automatically
0
0
0000
8-31