Fail-Safe Blocks
Error Information in Diagnostic Buffer
Error Code (W#16#...)
75DAH
8.6.6

F_M_AI6

Function
The F module driver reads the analog values (non-linearized values) and error
information of a 6-channel, fail-safe analog input module and makes the data
available to the associated F channel driver (F_CH_AI).
If there is a redundant module, the analog values of both modules are evaluated.
The F module driver is automatically inserted at the beginning of the run-time
group which also contains the associated F channel driver F_CH_AI. The I/Os of
the F block driver are automatically interconnected and supplied with values.
The outputs DIAG_1 and DIAG_2, at which error information is output, are
important.
I/Os
Name
Inputs:
CRC_IMP1
CRC_IMP2
TIMEOUT
MODE_00
...
MODE_05
RED
LADDR
LADDR_R
8-68
Description
Error in the safety data format (error due to online modification
of the Safety Program or internal CPU fault)
Data Type
Explanation
WORD
CRC via implicit data SM1
WORD
CRC via implicit data SM2
(only when RED = 1)
F_DINT
Monitoring time in ms for vital-
sign monitoring
F_WORD
Measurement range coding,
channel 0
F_WORD
Measurement range coding,
channel 5
F_BOOL
Module Redundancy
0: SM configured as non-
redundant
1: SM configured as redundant
INT
Logical address of the module
(SM1)
INT
Address of the configured
redundant SM2 module (only
when RED = 1)
Default
Supplied
automatically
Supplied
automatically
Supplied
automatically
Supplied
automatically
Supplied
automatically
Supplied
automatically
Supplied
automatically
Supplied
automatically
Fail-Safe Systems
A5E00085588-03