Mitsubishi MELSEC-A Series Reference Manual page 243

Type melsecnet, melsecnet/b data link system
Hide thumbs Also See for MELSEC-A Series:
Table of Contents

Advertisement

8.
PROCEDURES TO OPERATION
(2)
(3)
Test procedure
The following flowchart shows the operation procedure for station to station test.
Test result
The LEDs indicate the test result.
The descriptions of the LEDs are as follows.
(a) Normal... The following LEDs flash in order:
CRC, OVER, AB.IF, TIME, DATA, UNDER
(b) Error........The corresponding LEDs turn ON and the test is discontinued.
1) When the F.LOOP and TIME LEDs turn ON:
a) The forward loop cable is broken.
b) The sending and receiving ends of the forward loop are not
connected with a cable.
(2) When the F.LOOP, R.LOOP, and TIME LEDs turn ON:
a) The reverse loop cable is broken.
b) The sending and receiving ends of the reverse loop are not
connected with a cable.
c) The sending end of the forward loop is connected to the
sending end of the reverse loop, and the receiving end of the
forward loop is connected to the receiving end of the reverse
loop.
(3) When an ERROR LED other than 1) and 2) turns ON:
a) Hardware error
b) The cable was disconnected during the test.
c) A cable was broken during the test.
8 - 20

Advertisement

Table of Contents
loading

Table of Contents