207083
<location>Macro: ACX file not found
Message value:
Parameter: %1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The ACX file (macro) to be executed was not able to be found in the appropriate directory.
Fault value (r0949, interpret decimal):
Parameter number with which the execution was started.
See also: p0015, p0700 (Macro Binector Input (BI)), p1000 (Macro Connector Inputs (CI) for speed setpoints), p1500
(Macro Connector Inputs (CI) for torque setpoints)
Remedy:
- check whether the file is saved in the appropriate directory on the memory card.
Example:
If p0015 is set to 1501, then the selected ACX file must be located in the following directory:
... /PMACROS/DEVICE/P15/PM001501.ACX
207084
<location>Macro: Condition for WaitUntil not fulfilled
Message value:
Parameter: %1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The WaitUntil condition set in the macro was not fulfilled in a certain number of attempts.
Fault value (r0949, interpret decimal):
Parameter number for which the condition was set.
Remedy:
Check and correct the conditions for the WaitUntil loop.
207085
<location>Drive: Open-loop/closed-loop control parameters changed
Message value:
Parameter: %1
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SERVO_COMBI, SERVO_SINUMERIK828, SIC_COMBI,
SIC_SINUMERIK_828
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
Open-loop/closed-loop control parameters have had to be changed because:
1) They have exceeded dynamic limits because of other parameters, or
2) They cannot be used due to the hardware detected not having certain properties.
Fault value (r0949, interpret decimal):
The fault value includes the modified parameter number.
340: The motor and control parameters were automatically calculated (p0340 = 1), because the vector control was
subsequently activated as configuration (r0108.2).
See also: p0640 (Current limit), p1082 (Maximum speed), p1300 (Open-loop/closed-loop control operating mode)
Remedy:
It is not necessary to change the parameters as they have already been correctly limited.
640
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
Alarms