201485
<location>Topology: Comparison CX32 missing in the actual topology
Message value:
Component number: %1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a controller extension 32 (CX32) in the target topology that is not available in
the actual topology.
Alarm value (r2124, interpret decimal):
Component number of the additional target components.
Remedy:
- delete the CX32 / NX in the commissioning software project and download the new configuration to the drive unit.
- check that the actual topology matches the target topology and if required, change over.
- check DRIVE-CLiQ cables for interruption and contact problems.
- check the 24 V supply voltage.
- check that CX32/NX functions correctly.
Note:
Under "Topology --> Topology view" the commissioning software offers improved diagnostics capability (e.g. setpoint/
actual value comparison).
201486
<location>Topology: Comparison DRIVE-CLiQ components missing in the actual
topology
Message value:
Component number: %1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a DRIVE-CLiQ component in the target topology that is not available in the
actual topology.
Alarm value (r2124, interpret decimal):
Component number of the additional target components.
Remedy:
- delete the drive belonging to this component in the commissioning software project and download the new configu-
ration to the drive unit.
- re-configure the drive belonging to this component in the commissioning software project and download the new con-
figuration to the drive unit.
- check that the actual topology matches the target topology and if required, change over.
- check DRIVE-CLiQ cables for interruption and contact problems.
- check the 24 V supply voltage.
- check that the component is working properly.
Note:
Under "Topology --> Topology view" the commissioning software offers improved diagnostics capability (e.g. setpoint/
actual value comparison).
201487
<location>Topology: Comparison option slot components missing in the actual
topology
Message value:
Component number: %1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected an option slot module in the target topology that is not available in the actual
topology.
Alarm value (r2124, interpret decimal):
Component number of the additional target components.
552
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0