HMI alarms
120400
The settings for the acyclic links with the drive units are not yet effective.%nSwitch off/
on HMI !
Definitions:
A file transfer from/to a drive unit has failed as the settings for acyclic links with the drive units become effective only
after an HMI reboot.
Reaction:
Alarm display.
Remedy:
Switch off/on HMI and then repeat the process leading to the alarm.
Program
Internal
Continuation:
120401

SINAMICS: Write job for parameter %1, value %2, area %3: %4s timeout!

Parameters:
%1 = Number of parameter the value of which is to be written.
%2 = Value to be written
%3 = Area (drive object class to which the write job was addressed)
%4 = Time passed without the write job being acknowledged by the drive unit.
Definitions:
The write job of a SINAMICS parameter was not not acknowledged within 10 seconds by the drive unit.
If the write job is not acknowledged within the next 10 seconds, the alarm will again be triggered.
The waiting period for the acknowledgement of a write job is a maximum of 130 seconds, i.e. if the timeout specified
in the alarm is 130 seconds, it is assumed that the write job has failed. Otherwise it can be assumed that the write job
was successful despite the timeout.
Reaction:
Alarm display.
Remedy:
As long as the timeout specified in the alarm is less than 130 seconds, acknowledge alarm, otherwise switch off/on
control, drive system and HMI, and then repeat the process leading to the alarm.
Program
Internal
Continuation:
120402

Bus%1.Slave%2: %3: First commissioning of SINAMICS required!

Parameters:
%1 = Bus number
%2 = Slave address
%3 = Name of the affected drive unit
Definitions:
The drive unit with the bus number and slave address specified in the alarm is in 'First commissioning' state.
Reaction:
Alarm display.
Remedy:
Execute first commissioning for the affected drive unit.
To do so, switch in the HMI to the dialog 'First commissioning > Drive system > Drive unit, select the affected drive
unit, and follow the instructions of the HMI.
Program
Internal
Continuation:
502
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0