Sensor Diagrams - Roland Double Sheet Detector I100 Manual

For double sided sensors
Table of Contents

Advertisement

Technical data
2.3.1

Sensor diagrams

The marked areas represent the working ranges of the sensors. For all combinations of sheet
thickness and sensor distance Ax within the range a double sheet condition will be securely
detected, if the switching thresholds are set "tight". So it might be required to restrict the 1-sheet
detection range by changing the (factory-set) thresholds of 85% / 115% to approx. 95% / 105%.
The working ranges of the sensors depend very much on the material properties, they can deviate
from the sensor diagrams shown below.
S/E28
mm
15
Ax
10
AL
5
0
S/E34V
mm
40
30
Ax
20
Stainless steel (INOX)
10
0
1
S/E75
mm
60
50
Ax
40
FE
30
0
2
4
Fig. 5: Sensor diagrams for S/E sensors and MSI18S/E
Pos: 12 /Doppelblech/Kabel/S/E-Sensoren Kabelbelegung @ 0\mod_1185353919531_501.doc @ 4383 @ 33
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
14
Double Sheet Detector R100 I100
1
2
3
mm
Blechdicke
Sheet thickness
Nicht magnetischer
Edelstahl (INOX)
Non-magnetic
2
3
4
5
mm
Blechdicke
Sheet thickness
AL
6
8
10
12
14 15
mm
Blechdicke
Sheet thickness
Manual
for pairs of sensors
S/E34
mm
40
30
Ax
AL
20
FE
10
0
1
2
3
S/E54
mm
40
30
AL
Ax
FE
20
10
0
2
4
MSI18E/S (5KHz)
mm
40
AL
30
Ax
20
1,5
0
1
sensorsensordiagramme-S28-S75-deu-eng.wmf
B0003308 / 1.4 / 13.02.2013
4
5
6
mm
Blechdicke
Sheet thickness
6
8
10
mm
Blechdicke
Sheet thickness
2,5 mm
2
Blechdicke
Sheet thickness