Troubleshooting for FFQ Series
5.5
Thermistor or Related Abnormality
C4, C5, C9
Error Code
Method of Error
The temperatures detected by the thermistors determine thermistor errors.
Detection
Error Decision
The thermistor input is more than 4.96 V or less than 0.04 V during compressor operation.
Conditions
Disconnection of connector
Supposed
Defective thermistor corresponding to the error code
Causes
Defective indoor unit PCB
Troubleshooting
If the cause of the problem is related to the thermistors, the thermistors should be checked prior to
changing the indoor unit PCB.
To check the thermistors, proceed as follows:
C4 : Indoor heat exchanger thermistor 1 (liquid pipe) (R2T)
C5 : Indoor heat exchanger thermistor 2 (R3T)
C9 : Room temperature thermistor (R1T)
Refer to Thermistor Resistance / Temperature Characteristics table 1 on page 224.
171
Step
Action
1
Disconnect the thermistor from the indoor unit PCB.
2
Read the temperature and the resistance value.
Check if the measured values correspond with the values in the table of thermistor
3
resistance check.
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check the connection of
connectors.
Is it normal?
YES
Check the thermistor resistance
value.
Is it normal?
YES
NO
NO
SiUS181305E
Correct the connection.
Replace the thermistor.
(Replace the indoor unit PCB.)
Replace the indoor unit PCB.
(R19138)
Troubleshooting