Daikin RMXS-L Series Service Manual page 127

Multi-split 8-zone heat pump systems
Hide thumbs Also See for RMXS-L Series:
Table of Contents

Advertisement

SiUS181305E
Wireless Remote
1. Hold down the FILTER SIGN RESET (
Controller
(Factory Set is 1)
2. Press the FAN button and select A or b. Each time the button is pressed, the display switches
3. Press the UP button and DOWN button to set the address.
4. Press the RESERVE button to confirm the setting.
5. Hold down the INSPECTION/TEST button for at least 1 second to exit the field setting mode
Multiple Settings
When the indoor is controlled by outside controller (central remote controller, etc.), it sometimes
A/b
does not respond to ON/OFF command or temperature setting command from the remote
controller. Check what setting the customer needs and make the multiple setting as shown below.
Multiple Setting
A: Standard
b: Multiple display
Test Operation and Field Settings
same time for at least 4 seconds to enter the field setting mode. (SETTING is indicated on the
display).
between A and b.
Address can be set from 1 ~ 6, but set it to 1 ~ 3 and to same address as the receiver. (The
receiver does not work with address 4 ~ 6.)
and return to the normal display.
Field setting mode
Address
Multiple setting
Remote Controller
Remote Controller
Display
All items are displayed.
Operations set only is
displayed shortly after
execution.
) button and the INSPECTION/TEST button at the
Indoor Unit
Controlled by other air
conditioners or devices
ON/OFF command and
temperature setting
command cannot be
accepted. (1 long beep or
3 short beeps emitted)
All the commands can be accepted (2 short beeps)
Field Settings
(R14401)
Other condition
118