Thermistor Resistance / Temperature Characteristics
Table 2
Applicable
Outdoor unit
thermistor
FINTH: Radiation fin
Thermistor
temperature
Resistance (k)
°C (°F)
–30 (–22)
354.1
–25 (–13)
259.7
–20 (–4)
192.6
–15 (5)
144.2
–10 (14)
109.1
–5 (23)
83.25
0 (32)
64.10
5 (41)
49.70
10 (50)
38.85
15 (59)
30.61
20 (68)
24.29
25 (77)
19.41
30 (86)
15.61
35 (95)
12.64
40 (104)
10.30
45 (113)
8.439
50 (122)
6.954
55 (131)
5.761
60 (140)
4.797
65 (149)
4.014
70 (158)
3.375
75 (167)
2.851
80 (176)
2.418
85 (185)
2.060
90 (194)
1.762
95 (203)
1.513
100 (212)
1.304
105 (221)
1.128
110 (230)
0.9790
115 (239)
0.8527
120 (248)
0.7450
125 (257)
0.6530
130 (266)
0.5741
135 (275)
140 (284)
145 (293)
150 (302)
3PA61998
Drawing No.
(AD92A057)
225
Outdoor unit
R2T: Discharge pipe
Resistance (k)
4759
3454
2534
1877
1404
1059
806.5
618.9
478.8
373.1
292.9
231.4
184.1
147.4
118.7
96.13
78.29
64.10
52.76
43.63
36.26
30.27
25.38
21.37
18.06
15.33
13.06
11.17
9.585
8.254
7.131
6.181
5.374
4.686
4.098
3.594
3.161
3SA48009
(AD970175)
SiUS181305E