External Low Noise; Setting / Demand Setting; Night-Time Low Noise; Capacity Precedence Setting - Daikin RMXS-L Series Service Manual

Multi-split 8-zone heat pump systems
Hide thumbs Also See for RMXS-L Series:
Table of Contents

Advertisement

SiUS181305E
Setting Mode 2
Press the MODE (BS1) button for 5
seconds and enter the setting mode
2.
<Selection of setting items>
Press the SET (BS2) button and
select a setting item according to the
LED pattern shown in the table on
the right.
Press the RETURN (BS3) button
and decide the item. (The present
setting condition is shown.)
<Selection of setting conditions>
Press the SET (BS2) button and
select to the setting condition you
want.
Press the RETURN (BS3) button and
decide the condition.
Press the RETURN (BS3) button
and return to the initial status of
setting mode 2.
∗ If you become unsure of how to
proceed, press the MODE (BS1)
button and return to the setting
mode 1.
Test Operation and Field Settings
No.
Setting item
Cool / heat unified
1
address
Low noise / demand
2
address
Test operation
3
settings
Indoor unit forced
5
fan H
Indoor unit forced
6
operation
8
Te setting
9
Tc setting
Defrost changeover
10
setting

External low noise

12
setting / Demand
setting
13 AIRNET address
Setting of hot water
16
heater
Additional refrigerant
20
charge operation
setting
Refrigerant
recovery /
21
vacuuming mode
setting

22 Night-time low noise

setting
25 Setting of low noise
level
Night-time low noise
26
operation start
setting
Night-time low noise
27
operation end
setting
Power transistor
check mode
Check after
28
disconnection of
compressor wires
Capacity
29
precedence setting

30 Demand setting 1

32 Constant demand
setting
The numbers in the No. column represent the number of times to press the SET
(BS2) button.
Description
Sets address for cool / heat unified operation.
Address for low noise / demand operation
Used to conduct test operation without making changes to
the PCB and replacing the refrigerant, after the completion
of maintenance.
Allows forced operation of indoor unit fan while unit is
stopped. (H tap)
Allows forced operation of indoor unit.
Target evaporation temperature for cooling
Target condensation temperature for heating
Changes the temperature condition for defrost and sets to
quick defrost or slow defrost.
Reception of external low noise or demand signal
Set address for AIRNET.
Make this setting to conduct heating operation with hot
water heater.
Carries out additional refrigerant charge operation.
Sets to refrigerant recovery or vacuuming mode.
Sets automatic nighttime low noise operation in a simple
way.
The operating time is based on Starting Set and Ending Set.
Sets low noise level when the low noise signal is received.
Sets starting time of nighttime low noise operation.
(Night-time low noise setting is also required.)
Sets ending time of nighttime low noise operation.
(Night-time low noise setting is also required.)
Used for trouble diagnosis of DC compressor. Since the
waveform of inverter is output without wiring to the
compressor, it is convenient to probe whether the trouble
comes from the compressor or PCB.
If the capacity control is required, the low noise control is
automatically released by this setting during carrying out low
noise operation and nighttime low noise operation.
Changes target value of power consumption when demand
control 1 is received.
Enables demand control 1 without external input. (Effective
to prevent a problem that circuit breaker of small capacity is
shut down due to large load.)
Field Settings