21.2.3
B/P: propane/ butane mixture G30/ G31:
Fan settings must be changed by altering parameter P4BD (display D8). (Only by a Competent Engineer).
The CO
level must not be in the hatched area.
2
EF80-120
____________________________________________________________________________
EF150
____________________________________________________________________________
CO
2
10,6 %
max load
10,4 %
9,3 %
min load
9,1 %
CO
2
10,7 %
max load
10,5 %
9,3 %
min load
9,1 %
adjust
O.K.
adjust
adjust
O.K.
adjust
adjust
O.K.
adjust
adjust
O.K.
adjust
O
2
5,1 %
5,4 %
7,0 %
7,3 %
O
2
4,9 %
5,2 %
7,0 %
7,3 %