Flow Monitoring; Water Pressure Switch; Electrical Supply; Connector Strip - Lochinvar EcoForce EF80 Installation, Commissioning, User And Maintenance Instructions

Wall mounted gas fired condensing water heater
Table of Contents

Advertisement

F
M
LOW
ONITORING
If the water flow through the heat exchanger drops and the temperature differential is too high, the water heater will shut down until the
differential drops during this time the display shows the message DELTA DIRECT BLOCK. If this situation occurs more than four times, the
water heater will lock out and will display the message FLOWRETURN DT FAULT. Upon resetting the water heater, the output will be limited
to 50% in order to protect the heat exchanger.
If this situation occurs, please contact Lochinvar Technical support immediately for further guidance.
W
P
ATER
RESSURE
The EcoForce water heater is fitted with a water pressure switch that will block the water heater from operating at pressures less than 0.75bar
to protect the heat exchanger from damage. The display will show the following message:
Display message
Reason

ELECTRICAL SUPPLY

Wiring external to the equipment must be installed in accordance with the I.E.E. Regulations and any local regulations that apply.
Model
EF80
EF100
EF120
EF150
EF180
11.1.1
Electrical supply requirements
WARNING: THIS APPLIANCE MUST BE EARTHED
A suitably competent person MUST check wiring. Normal supply required is 230 volts AC, single phase, 50 Hz. An isolator with a
contact separation of at least 3mm in all poles should be sited close to the equipment and must only serve that equipment. The
double pole switch must be readily accessible under all conditions.
C
S
ONNECTOR
TRIP
TANK
SENSOR
S
WITCH
W a
t
e
r
p
Water pressure is too low or high.
Normal Supply Voltage
230V AC
r
e
s
s u
r
e
9
9
External Fuse Rating
50 Hz
1 PH
f
a u
l
t
9
,
5
h
r
s
6.0 Amps
Power Consumption
136W
142W
151W
214W
229W