M
P
INIMUM
IPE HEADER
The below pipe header sizes are recommended, these should be checked against the available head on the pump and the proposed
pipework run.
MODEL
EF80
EF100
EF120
EF150
EF180
10.7.1
PIPEWORK HEADER SIZES FOR COMMON INSTALLATIONS
10.7.2
10.7.3
S
IZING
PIPEWORK A BLUE SIZE (mm)
1
42
54
54
54
54
Pipework schematic showing pipework A and pipework B on single model
Pipework schematic showing pipework A and pipework B on multiple models
NUMBER OF FORCE
2
54
54
54
67
67
A
A
B
PIPEWORK B RED SIZE (mm)
3
54
67
67
76
108
A
A
4
67
67
76
108
108
45